journal article·2025-06-02Open access

Experimental Study on Fire-Resistance Performance Depending on the Applied Volume of Firestop Material in Metallic and Nonmetallic Penetration Systems

Hong-Beom Choi, A-Yeong Jeong, Jin-O Park, Seung-Yong Hyun, Hyung-Do Lee

Applied Sciences· Volume 15· Issue 11

Abstract

This study aims to improve firestop application standards by experimentally analyzing changes in fire-resistance performance due to variations in opening size, penetrant diameter, and firestop material volume. Fire-resistance tests were conducted for 120 min in accordance with KS F ISO 10295-1, using eight specimens with systematically varied cross-sectional areas of openings and penetrants. For nonmetallic pipes, which soften or melt at elevated temperatures, the results show that the completeness of the opening seal and the amount of firestop material are the primary factors governing fire resistance. When the firestop-to-opening area ratio decreased from 95–91%, the maximum temperature on the unexposed surface was, on average, 15–30 °C lower, confirming that modest reductions in firestop material volume for small openings do not compromise performance. In contrast, metallic pipes retained structural integrity and acted as direct heat-transfer paths; fire-resistance performance was more strongly influenced by penetrant diameter and cross-sectional area than by opening size. These findings provide quantitative evidence to support flexible design criteria for firestop systems and offer a practical basis for transitioning toward performance-based approval standards.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Fire effects on concrete materials · Combustion and Detonation Processes

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Korea Institute of Civil Engineering and Building Technology, Goyang-si 10223, Republic of Korea

Funding

Korea Institute of Civil Engineering and Building Technology

References (23)

Show source-provided references
1. Analysis of Causes of Casualties in Jecheon Sports Center Fire—Focus on Structural Factors of Buildin10.7731/KIFSE.2018.32.4.086 ↗
2. Promat (2025, April 25). The Passive Fire Protection Handbook: The UK’s Comprehensive Guide to Passive Fire Protection. Available online: https://www.promat.co.uk/en/reference/fire-protection-handbook.
3. Estimation of effective thermophysical properties of firestopping sealants: Methodology and case study10.1016/j.firesaf.2023.103928 ↗
4. Problematyka prawidłowego odbioru wybranych oddzieleń przeciwpożarowych
5. Badania odporności ogniowej dużych mieszanych uszczelnień przejść instalacyjnych
6. Gillespie, P.E., O’Leary, P.E., Mattes, B., Talbot, J., Neese, R.K., and Wasilewski, B. (2025, April 25). Technical Guideline on Through Penetration Firestopping. Available online: https://www.smacna.org/business-resources/resource/technical-guideline-on-through-penetration-firestopping.
7. Fire-stop wraps and collars with intumescent materials—Performance comparison10.1016/j.proeng.2017.02.113 ↗
8. Bezpieczeństwo pożarowe, Cz.17: Przejścia instalacyjne
9. Temperatura uszczelnień przejść rur metalowych przez ściany i stropy w badaniach odporności ogniowej
10. Rozwiązania techniczne przejść instalacyjnych z uwagi na bezpieczeństwo pożarowe
11. Porównanie skuteczności działania opasek i kołnierzy ogniochronnych z materiałami pęczniejącymi
12. Problematyka prawidłowego odbioru uszczelnień przejść instalacyjnych
13. A study on assessment of penetration seals performance of nuclear power plants
14. Standard supporting and F-class structures for improving the firestop recognition system10.9798/KOSHAM.2019.19.5.127 ↗
15. Lee, J. (2022). Evaluation of Heat Insulation Material Performance Based on Firestop System Thermal Modeling. [Ph.D. Thesis, Department of Architectural Engineering, Kwangwoon University].
16. Experimental study on the fire performance of firestop systems for through-penetrations in fire-rated walls
17. (2021). Standard Test Method for Fire Tests of Penetration Firestop Systems (Standard No. ASTM E814).
18. (2021). Standard for Fire Tests of Through-Penetration Firestops (Standard No. UL 1479).
19. Improvement plans for fire-resistant structures in buildings
20. (2021). Fire Tests for Penetration Seals—Part 1: Fire Resistance Test Method (Standard No. KS F ISO 10295-1).
21. (2022). Fire-Resistance Tests—Elements of Building Construction—Part 1: General Requirements (Standard No. KS F ISO 834-1).
22. (2021). Carbon Steel Pipes for Pressure Service (Standard No. KS D 3562).
23. (2021). Unplasticized Polyvinyl Chloride (PVC-U) Pipes for Water Supply (Standard No. KS M 3404).