Abstract
As the penetration rate of clean energy gradually increases, the demand for flexible regulation resources in the power grid is increasing accordingly. The variable-speed pumped storage unit with a full-size converter (FSC-VSPSU) can provide fast and flexible regulation resources for the power grid, which assists in the stable operation of the clean-energy-dominated power systems. Thus, its application is gradually becoming widespread. FSC-VSPSU relies on the power electronic converter for grid connection. When the impedance mismatch between FSC-VSPSU and the power grid occurs, the grid-connected system will experience oscillations, which seriously threatens its safe and stable operation. Aiming at this, this article firstly relies on the SISO impedance measurement and an equivalent impedance analysis to obtain the stability analysis criterion. Furthermore, applying the impedance matching analysis with the Bode diagram, the influence rules of the parameters of the grid-connected FSC-VSPSU on oscillation are obtained. In addition, with the summarized oscillation analysis results, this study delves into an exploration of pertinent strategies for oscillation suppression. Finally, a grid-connected FSC-VSPSU simulation model is built in MATLAB/SIMULINK, and the simulation results verify the correctness of the oscillation analysis results and the effectiveness of the proposed oscillation suppression strategy.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Microgrid Control and Optimization · Smart Grid Energy Management · HVDC Systems and Fault Protection
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Sichuan Electrical Power Research Institute, Chengdu 610041, China
State Grid Sichuan Electric Power Company, Chengdu 610095, China
School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China
Funding
Science and Technology Project of State Grid Sichuan Electric Power Company · Sichuan Science and Technology Program
References (26)
Show source-provided references
1. A sliding mode based damping control of dfig for interarea power oscillations10.1109/TSTE.2016.2597306 ↗
2. Voltage harmonics optimization for weak grid-tied doubly-fed induction generator with the capability of suppressing current harmonics10.1109/TEC.2022.3233843 ↗
3. Performance analysis of a 10 mw wind farm in providing secondary frequency regulation: Experimental aspects10.1109/TPWRS.2019.2891962 ↗
4. Coordinated multi-objective optimization for multiple trade-offs in pumped outage condition of pumped storage system10.1109/ACCESS.2019.2951628 ↗
5. Nie, G., Liu, C., and Sun, Z. (2023, January 28–30). Optimization method of hybrid energy storage configuration for pumped storage power station based on spectrum analysis. Proceedings of the 2023 3rd International Conference on Energy Engineering and Power Systems (EEPS), Dali, China.10.1109/EEPS58791.2023.10256789 ↗
6. Yang, Z., Zhang, Y., Li, B., Ma, X., Zhang, X., Ma, Y., Guo, S., and Kong, X. (2022, January 16–18). Surface deformation monitoring and identification of potential geological hazards in Funing pumped storage power station based on Time Series InSAR. Proceedings of the 2022 IEEE 5th Advanced Information Management, Communicates, Electronic and Automation Control Conference (IMCEC), Chongqing, China.
7. A regulating capacity determination method for pumped storage hydropower to restrain PV generation fluctuations
8. Li, W., Qiao, J., Wang, Y., Liu, R., Lv, T., and Yin, X. (2022, January 22–24). Fault diagnosis method of stator windings short circuit for variable speed pumped storage unit based on park transform. Proceedings of the 2022 5th International Conference on Energy, Electrical and Power Engineering (CEEPE), Chongqing, China.10.1109/CEEPE55110.2022.9783305 ↗
9. Control methods for operation of pumped storage plants with full-size back-to-back converter fed synchronous machines10.1109/TIA.2023.3305324 ↗
10. Modeling and transient response analysis of doubly-fed variable speed pumped storage unit in pumping mode10.1109/TIE.2022.3224154 ↗
11. Jian, Y., Zhong, L., Yi, F., Guo, H., Yang, H., Xu, W., Hu, J., and Wu, Y. (2022, January 23–25). Feasibility analysis of full power variable speed operation of pumped storage power station based on M3C converter. Proceedings of the 2022 12th International Conference on Power and Energy Systems (ICPES), Guangzhou, China.10.1109/ICPES56491.2022.10073170 ↗
12. Li, D., Gong, G., Lv, J., Jiang, X., and He, R. (November, January 30). An overall control of doubly fed variable speed pumped storage unit in pumping mode. Proceedings of the 2020 IEEE 4th Conference on Energy Internet and Energy System Integration (EI2), Wuhan, China.10.1109/EI250167.2020.9346705 ↗
13. Pan, P., Ding, L., Shi, H., and Chen, G. (2023, January 27–30). Multi-mode simulation modeling of full-size variable speed pumped storage system including the complete unit links. Proceedings of the 2023 Panda Forum on Power and Energy (PandaFPE), Chengdu, China.10.1109/PandaFPE57779.2023.10141334 ↗
14. Impacts of dynamic frequency feedback loop in SOGI-PLL on low-frequency oscillation in an electric railway system10.1109/TTE.2023.3234697 ↗
15. Low-frequency oscillation in electric railway depot: A comprehensive review10.1109/TPEL.2020.2998702 ↗
16. Impacts of quadrature signal generation-based plls on low-frequency oscillation in an electric railway system10.1109/TTE.2021.3086231 ↗
17. Impedance modeling and stability analysis of a three-phase three-level NPC inverter connected to the grid
18. Harmonic instability analysis and suppression method based on αβ- frame impedance for trains and network interaction system10.1109/TEC.2018.2882804 ↗
19. Stability analysis and impedance reshaping method for DC resonance in VSCs-based power system10.1109/TEC.2021.3066201 ↗
20. A novel forbidden-region-based stability criterion in modified sequence-domain for AC grid-converter system10.1109/TPEL.2018.2869422 ↗
21. Impedance measurement of three-phase inverter in the stationary frame using frequency response analyzer10.1109/TPEL.2020.2974805 ↗
22. A novel controlled frequency band impedance measurement approach for single-phase railway traction power system10.1109/TIE.2019.2896297 ↗
23. Rapid impedance measurement approach based on wideband excitation for single-phase four-quadrant converter of high-speed train10.1109/TIM.2021.3107048 ↗
24. Rapid dq-frame impedance measurement for three-phase grid based on interphase current injection and fictitious disturbance excitation10.1109/TIM.2022.3217851 ↗
25. Harmonic-domain siso equivalent impedance modeling and stability analysis of a single-phase grid-connected VSC10.1109/TPEL.2020.2970390 ↗
26. An improved controlled-frequency-band impedance measurement scheme for railway traction power system10.1109/TIE.2020.2972469 ↗