Phase Risk Analysis of Overhead Lines Under Complex Icing Conditions
Source abstract
Abstract
Phase-to-ground discharge of transmission lines due to ice cover is a common issue. To assess the risk of phase-to-ground discharge of overhead lines under complex ice-covering conditions, this study used finite element analysis to model the interaction between ground wire, conductor, and insulator. The study examined how different factors affect the minimum safe distance between the conductor and ground wire, as well as the risk coefficient of phase-to-ground discharge and the risk zone. The finding reveals that as icing thickness increases, conductor bouncing intensifies, reducing the phase-to-ground distance, and placing one half of the line span within the risk zone for the given conditions. For the same length of de-icing, the closer the de-icing region is to the midpoint, the greater is the maximum jump height of the conductor. When the span is extended to 600 m, the risk range covers approximately 70% of the total line length. Under strong winds, conductor lateral displacement increases with wind speed, which leads to a higher risk of discharge.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Icing and De-icing Technologies · Thermal Analysis in Power Transmission · Mechanical stress and fatigue analysis
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Power Science Research Institute of State Grid Xinjiang Electric Power Co., Ltd., Urumqi 830011, China
School of Electronic Information, Xi’an Polytechnic University, Xi’an 710048, China
Funding
State Grid Xinjiang Electric Power Co., Ltd.
References (16)
Show source-provided references
1. Dynamic response of a transmission conductor following delayed ice shedding by reduced-scale model test10.1016/j.coldregions.2024.104288 ↗
2. Zhang, Z., Zhang, H., Yue, S., and Zeng, W. (2023). A Review of Icing and Anti-Icing Technology for Transmission Lines. Energies, 16.10.3390/en16020601 ↗
3. Research on Uneven Iced Transmission Lines and the Dynamic Response after Ice-shedding
4. Research on the Scheme of Overhead Ground Wire Lightning Protection and Melting⁃ice System
5. Chen, Y., Fan, S., Wang, X., Yu, J., Song, P., and Lu, Y. (2024). Anti-icing Technology for Transmission Lines Based on New Ground Wire Structures and Operation Modes. High Volt. Eng., 1–10.
6. Dynamic Analysis of Overhead Power Lines after Ice-Shedding Using Finite Element Method
7. Dynamics of digitally controlled forced vibration of suspended cables10.1007/s11012-022-01627-0 ↗
8. Numerical modelling of the dynamic response of ice-shedding on electrical transmission lines10.1016/S0169-8095(97)00046-X ↗
9. Jump height of an iced transmission conductor considering joint action of ice-shedding and wind10.1016/j.coldregions.2022.103576 ↗
10. Research of Ice-shedding Response of Transmission Lines Under Strong Winds
11. Dong, X., Zhao, M., Li, M., and Zhu, Y. (2024). Study on the Bouncing Process Induced by Ice Shedding on Overhead Conductors under Strong Wind Conditions. Appl. Sci., 14.10.3390/app14104285 ↗
12. Xu, G. (2016). Numerical Simulation Study of Iced Conductor on Dynamic Response of Ice-Shedding on Transmission Lines, Xi’an Polytechnic University.
13. Technical Regulations for Design of Tower Structures of Overhead Transmission Lines (Standard No. DL/T5154-2012). Available online: https://www.chinesestandard.net/PDF/English.aspx/DLT5154-2012.
14. Shao, T. (2003). Mechanical Calculation of Overhead Power Transmission Lines, China Electric Power Press.
15. Calculation of jump height for uneven ice-shedding of overhead transmission lines
16. Technical Code for Design of Long Span Crossing of 110 kV~750 kV Overhead Transmission Line (Standard No. DL/T 5485-2013). Available online: https://www.chinesestandard.net/PDF/English.aspx/DLT5485-2013.