journal article·2024-10-05Open access

The Role of AC Resistance of Bare Stranded Conductors for Developing Dynamic Line Rating Approaches

Jordi-Roger Riba

Applied Sciences· Volume 14· Issue 19

Abstract

Overhead transmission line conductors are usually helically stranded. The current-carrying section is made of aluminum and/or aluminum alloys. Several factors affect their electrical resistance, such as the conductivity of the conductor material, the cross-sectional area, the lay length of the different layers of aluminum, and the presence of a steel core used to increase the mechanical strength of the conductor. The direct current (DC) and alternating current (AC) resistances per unit length of stranded conductors are different due to the effect of the eddy currents. In steel-reinforced conductors, there are other effects, such as the transformer effect due to the magnetization of the steel core, which make the AC resistance dependent on the current. Operating temperature also has an important effect on electrical resistance. Resistive losses are the main source of heating in transmission line conductors, so their temperature rise is highly dominated by such power losses, making it critical to know the value of the AC resistance per unit length when applying dynamic line rating (DLR) methods. They are of great interest especially in congested lines, as by applying DLR approaches it is possible to utilize the full line capacity of the line. This paper highlights the difficulty of accurately calculating the electrical resistance of helically stranded conductors, especially those with a magnetic core, and the importance of accurate measurements for the development of conductor models and DLR approaches.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Thermal Analysis in Power Transmission · Power Line Communications and Noise · Lightning and Electromagnetic Phenomena

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Campus Terrassa, Universitat Politècnica de Catalunya, Rambla Sant Nebridi 22, 08222 Terrassa, Barcelona, Spain

Funding

Generalitat de Catalunya · Ministerio para la Transformación Digital y de la Función Pública

References (33)

Show source-provided references
1. (2008). Alternating Current (AC) Resistance of Helically Stranded Conductors, Cigré. Technical Brochure 345.
2. Castro, P., Lecuna, R., Manana, M., Martin, M.J., and Del Campo, D. (2020). Infrared Temperature Measurement Sensors of Overhead Power Conductors. Sensors, 20.10.3390/s20247126 ↗
3. Analyzing the Role of Emissivity in Stranded Conductors for Overhead Power Lines10.1016/j.ijepes.2024.110027 ↗
4. PMU-Based Cable Temperature Monitoring and Thermal Assessment for Dynamic Line Rating10.1109/TPWRD.2020.3016717 ↗
5. Application of Digital Elevation Models to Wind Estimation for Dynamic Line Rating10.1016/j.ijepes.2021.107338 ↗
6. Deep Learning-Based Cyber Resilient Dynamic Line Rating Forecasting10.1016/j.ijepes.2022.108257 ↗
7. Riba, J.-R. (2023). Radial Thermoelectric Model for Stranded Transmission Line Conductors. Sensors, 23.10.3390/s23229205 ↗
8. Thermal Behaviour of Medium-Voltage Underground Cables under High-Load Operating Conditions10.1016/j.applthermaleng.2019.04.083 ↗
9. Dependence of the Contact Resistance on the Design of Stranded Conductors10.3390/s140813925 ↗
10. (2023). Electric Cables—Calculation of the Current Rating—Part 1-1: Current Rating Equations (100 % Load Factor) and Calculation of Losses—General (Standard No. IEC IEC 60287-1-1:2023).
11. Kirkpatrick, L. (1989). Aluminum Electrical Conductor Handbook, The Aluminum Association. [3rd ed.].
12. (1996). Aluminium Conductors for Overhead Transmission Purposes—Specification Part 1 Aluminium Stranded Conductors (Standard No. Indian Standards IS 398).
13. Cigré Working Group 22.12 (2002). Thermal Behaviour of Overhead Conductors, Cigré.
14. (2001). Conductors for Overhead Lines—Round Wire Concentric Lay Stranded Conductors (Standard No. CENELEC EN 50182:2001).
15. The Resistance and Reactance of Aluminum Conductors, Steel Reinforced
16. Analysis of Formulas to Calculate the AC Resistance of Different Conductors’ Configurations10.1016/j.epsr.2015.05.023 ↗
17. The Alternating-Current Resistance of Parallel Conductors of Circular Cross-Section
18. (2012). IEEE Standard for Calculating the Current-Temperature of Bare Overhead Conductors (Standard No. IEEE Std 738-2012).
19. Riba, J.R.R., Liu, Y., Moreno-Eguilaz, M., and Sanllehí, J. (2022). On-Line Core Losses Determination in ACSR Conductors for DLR Applications. Materials, 15.10.3390/ma15176143 ↗
20. AC Resistance of ACSR—Magnetic and Temperature Effects: Prepared by a Task Force of the Working Group on Calculation of Bare Overhead Conductor Temperatures10.1109/MPER.1985.5526666 ↗
21. Experimental Study on the Transformer Effect in an ACSR Cable10.1016/j.ijepes.2020.105861 ↗
22. Effect of Magnetic Induction in a Steel-Cored Conductor on Current Distribution, Resistance and Power Loss10.1109/61.637007 ↗
23. The Current Distribution, Resistance and Internal Inductance of Linear Power System Conductors—A Review of Explicit Equations10.1109/TPWRD.2012.2213617 ↗
24. Magnetic Properties of an ACSR Conductor Steel Core at Temperatures up to 230 °C and Their Impact on the Transformer Effect10.1049/smt2.12016 ↗
25. AC Resistance of ACSR—Magnetic and Temperature Effects10.1109/TPAS.1985.319175 ↗
26. The Effect of Frequency on the Resistance and Internal Inductance of Bare Acsr Conductors10.1109/61.85881 ↗
27. Lv, F., Zhang, P., Tang, Z., Yue, Y., and Yang, K. (2019). A Guided Wave Transducer with Sprayed Magnetostrictive Powder Coating for Monitoring of Aluminum Conductor Steel-Reinforced Cables. Sensors, 19.10.3390/s19071550 ↗
28. Sequential Estimation of the Radial Temperature Variation in Overhead Power Cables
29. Papailiou, K.O. (2017). Overhead Lines, Cigré Green Books.10.1007/978-3-319-31747-2 ↗
30. Rahman, S.A., and Kopsidas, K. (2017, January 18–22). Modelling of Convective Cooling on Conductor Thermal Rating Methods. Proceedings of the 2017 IEEE Manchester PowerTech, Manchester, UK.10.1109/PTC.2017.7981007 ↗
31. (2012). Standard Specification for Aluminum 1350 Drawing Stock for Electrical Purposes (Standard No. ASTM B233).
32. (1991). Round Wire Concentric Lay Overhead Electrical Stranded Conductors (Standard No. IEC IEC 61089:1991).
33. American Wire Group (2024, May 11). ACSR Aluminum Conductor Steel Reinforced. Available online: https://www.buyawg.com/item/bare-aluminum-acsr/acsr-aluminum-conductor-steel-reinforced/swanate.