Evaluation of Structural Performance of Post-Installed Anchors Embedded in Cracked Concrete in Power Plant Facilities

Sangmoon Lee, Wooyoung Jung

Applied Sciences· Volume 11· Issue 8

Abstract

In this study, a field survey was conducted on the fixed anchorages of the operation and power generation facilities installed in domestic power plants. A static/dynamic performance evaluation was conducted to present safety evaluation guidelines that meet the domestic seismic performance requirements. Seismic performance tests were performed on the post-installed set anchors M10 and M12, which are mainly used for anchorages in accordance with the US and European seismic performance standards. The dynamic shear test results showed that the M12 anchor met the seismic performance verification criterion, whereas the M10 anchor did not because its dynamic performance was reduced, owing to the cyclic loading. In the results of the dynamic pull-out test, M12 also met the seismic performance verification criterion, whereas M10 was safe only in a non-cracked state. In summary, the seismic performance of M12 in both cracks and non-cracks was satisfied, but, in the case of M10, the results were not satisfied in cracks. This was an experimental study; it will be necessary to conduct additional analytical research in the future to verify the reliability and parameters of the experiment.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Seismic Performance and Analysis · Structural Behavior of Reinforced Concrete · Structural Load-Bearing Analysis

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Civil Engineering, Gangneung-Wonju National University, Gangneung 210-702, Korea

Funding

Ministry of Land, Infrastructure and Transport

References (13)

Show source-provided references
1. Performance Evaluation of the Post-Installed Anchor for Sign Structure
2. Evaluation of anchorage performance of the switchboard cabinet under seismic loading condition10.1177/1687814020926309 ↗
3. (2012). Reducing the Risks of Nonstructural Earthquake Damage—A Practical Guide, FEMA E-74.
4. Seismic Damage Status and Characteristics of Non-structural Elements
5. A Study on the Concrete Breakout Capacity Evaluation of Medium-to-Large size CIP Anchor Bolts under Tension Loading
6. (2011). Building Code Requirements for Structural Concrete (ACI 318-11) and Commentary, ACI. ACI Committee 318.
7. A Study on the Evaluation of Concrete Breakout Strength for Cast-In-Place Anchor with Crack
8. Static Shear Resistance of Cast-In-Place Anchors in Cracked Concrete10.7781/kjoss.2015.27.3.347 ↗
9. (2002). Evaluating the Performance of Post-Installed Mechanical Anchors in Concrete, Reported by ACI Committee 355, ACI. ACI 355.2-01.
10. Behavior of post-installed anchors tested by stepwise increasing cyclic crack protocols10.14359/51689431 ↗
11. (2016). Post-Installed Fasteners in Concrete under Seismic Action, EOTA. EOTA TR 049.
12. Sleeve-type expansion anchor behavior in cracked and uncracked concrete10.1016/j.nucengdes.2003.06.018 ↗
13. (2003). Standard Test Methods for Strength of Anchors in Concrete and Masonry Elements, ASTM. ASTM E 488-96.