Heat release rate of wooden cribs with water application for fire suppression
Source abstract
Abstract
Abstract A series of experiments was conducted in order to measure the maximum heat release rate of a wood crib ignited at the center of its base after water applications which were not sufficient to extinguish the wood crib fire. The novelty of the present experiments lies in distributing the water uniformly just above the top surface thus ensuring what the exact delivery density is. Uniform water distribution was produced by a system of pipes with holes 5 cm above the wood crib. The variable experimental parameters were the number of layers of wood cribs (6, 9, 12), the water delivered density, and the water activation time. The size of the wood sticks is fixed and they are layered in a fixed staggered way alternating at 9 or 10 sticks per layer. Regardless of the number of wood crib layers, the reduction of the maximum heat release rate by water supplication was proportional to the total water flow rate W ˙ . The constant of proportionality is approximately 12 kJ/g in these experiments for all water delivered densities and all numbers of layers of wood cribs where water was applied either earlier or just when the maximum heat release rate was reached in the free burning wood crib fires. The proportionality factor 12 kJ/g is explained by noting that the heat removed per unit time by the completely evaporated water is proportional to the water application rate times the heat of evaporation and that this leads to the reduction of mass loss rate to be proportional to the water application rate multiplied by the heat of evaporation and divided by the heat of pyrolysis of wood. Therefore, the reduction of heat release rate is equal to the reduction of the mass loss rate multiplied by the heat of combustion of wood. In addition, data for the total heat released and the total mass loss also support the proposition that the reduction in the total heat release is due to the extinction of the wood crib burning area being proportional to the water supply rate. We expect that these results to be applicable as long as the burning of wood crib is fuel controlled.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire effects on ecosystems · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (23)
Show source-provided references
1. Extinguishment of rack storage fires of corrugated cartons using water
2. Madrzykowski
3. British Automatic Sprinkler Association, Arup Fire
4. Arvidson · 2002
5. Evans
6. The development of the ESFR sprinkler system10.1016/0379-7112(88)90045-8 ↗
7. Experiments and theory of the extinction of a wood crib
8. Suppression effectiveness of water-mist sprays on accelerated wood-crib fires10.1016/j.firesaf.2014.08.012 ↗
9. The role of water in suppression of fires
10. Suppression of rack-storage fires by water
11. Expected size of shielded fires in sprinklered office buildings
12. Fire growth rate in wood cribs10.1016/0010-2180(76)90028-6 ↗
13. NFPA · 1986
14. Walton
15. The extinction of fire with plain water
16. Flammability of Plastics-I burning intensity10.1016/0010-2180(76)90059-6 ↗
17. Drysdale · 1986
18. Heat release rate of combustible material suppressed by water ∼part.1 experiments by using sprinkler system
19. Relation between heat release rate and radiative heat flux of wooden crib burning during water discharge10.3210/fst.30.1 ↗
20. A study on control of compartment fire, part 6 Heat release rate controlled by sprinkler
21. Kida · 1973
22. Fire extinguishment time by sprinkler
23. Required delivered density (RDD) and Actual delivered density (ADD) of crib fire