Stairwell smoke transport in a full-scale high-rise building: Influence of opening location
Source abstract
Abstract
Abstract In this study, a series of experiments were conducted with varying number of pool fires and opening location (floor with ventilation openings) in a 21-story full-scale office building to study the transport phenomena and stratification of hot smoke in the stairwell. The experiments show that the flame of the pool fire inclines away from the side lobby door as pushed by the side air entrainment. The strength of stack effect in the stairwell initially increases, then decreases with the opening height increases. The rise in temperature in the stairwell can be divided into a lower and an upper region, depending on the location and attenuation effect of the upper opening. In the lower region, both the stack effect and turbulent mixing play important roles in the movement of hot smoke, whereas in contrast, in the upper region, turbulent mixing dominates. The equivalent heat release rate for hot smoke in the upper region is determined through theoretical analysis, and an integrated correlation is proposed for predicting the rise time of the smoke plume in the stairwell. These unique full-scale experiments provide crucial experimental data and empirical correlations that help the design of safer smoke ventilation systems for stairwells in a high-rise building.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Wind and Air Flow Studies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (37)
Show source-provided references
1. 9/11 world trade center attacks: lessons in fire safety engineering after the collapse of the towers10.1007/s10694-013-0337-6 ↗
2. Toxicity of fire smoke10.1080/20024091064246 ↗
3. Assessment of the fire toxicity of building insulation materials10.1016/j.enbuild.2010.10.015 ↗
4. A new model for determining neutral-plane position in shaft space of a building under fire situation10.1016/j.buildenv.2007.02.004 ↗
5. Enhancement of natural ventilation in high-rise residential buildings using stack system10.1016/S0378-7788(03)00076-8 ↗
6. Fire-induced smoke control via hybrid ventilation in a huge transit terminal subway station10.1016/j.enbuild.2011.11.018 ↗
7. A study on the development and application of the E/V shaft cooling system to reduce stack effect in high-rise buildings10.1016/j.buildenv.2009.06.011 ↗
8. Stack effect of smoke for an old-style apartment in Taiwan10.1016/j.buildenv.2011.04.026 ↗
9. The instability of liquid surfaces when accelerated in a direction perpendicular to their planes. I
10. A simple experiment to investigate two‐dimensional mixing by Rayleigh–Taylor instability10.1063/1.857652 ↗
11. Air entrainment into smoke and hot gases in open shafts10.1016/0379-7112(86)90030-5 ↗
12. Cannon · 1975
13. Simulating smoke movement through long vertical shafts in zone-type compartment fire models10.1016/S0379-7112(98)00070-8 ↗
14. Investigation into rise time of buoyant fire plume fronts
15. Experimental study on influence of stack effect on fire in the compartment adjacent to stairwell of high rise building10.3846/13923730.2013.802729 ↗
16. Experimental investigation on the characteristics of buoyant plume movement in a stairwell with multiple openings10.1016/j.enbuild.2013.09.028 ↗
17. Study of FDS simulations of buoyant fire-induced smoke movement in a high-rise building stairwell10.1016/j.firesaf.2017.04.005 ↗
18. Experimental investigation on the rising characteristics of the fire-induced buoyant plume in stairwells10.1016/j.ijheatmasstransfer.2013.04.030 ↗
19. Transport characteristics of thermal plume driven by turbulent mixing in stairwell10.1016/j.ijthermalsci.2014.11.009 ↗
20. Influence of relative location of two openings on fire and smoke behaviors in stairwell with a compartment10.1016/j.ijthermalsci.2014.10.008 ↗
21. Experimental investigation of combustion characteristics under different ventilation conditions in a compartment connected to a stairwell10.1016/j.applthermaleng.2016.01.117 ↗
22. Deflection characteristic of flame with the airflow induced by stack effect10.1016/j.ijthermalsci.2017.01.024 ↗
23. Studies on smoke movement in stairwell induced by an adjacent compartment fire10.1016/j.applthermaleng.2009.01.009 ↗
24. Buoyancy-driven flow through a stairwell10.1016/S0360-1323(99)00062-1 ↗
25. Experimental and numerical study of buoyancy-driven stairwell flow in a three storey building10.1016/S0360-1323(01)00060-9 ↗
26. Comparison of FDS prediction of smoke movement in a 10-Storey building with experimental data10.1007/s10694-008-0075-3 ↗
27. Wang · 2008
28. Numerical simulation of fire-induced flow through a stairwell10.1016/j.buildenv.2004.07.011 ↗
29. Transport phenomena of fire-induced smoke flow in a semi-open vertical shaft10.1108/HFF-12-2017-0514 ↗
30. Influence of fire power and window position on smoke movement mechanisms and temperature distribution in an emergency staircase10.1016/j.enbuild.2014.02.083 ↗
31. Numerical investigation of external wind effect on smoke characteristics in a stairwell10.1007/s10694-020-00948-4 ↗
32. A comparative study on the influence of ventilation on weather- and fire-induced stack effect in the elevator shafts of a high-rise building10.1007/s10694-017-0679-6 ↗
33. Hamins · 1999
34. Combustion heat release analysis of ethanol or n-butanol diesel fuel blends in heavy-duty DI diesel engine10.1016/j.fuel.2010.12.003 ↗
35. Standard · 1999
36. Effects of radiation on temperature measurement in a fire environment10.1177/073490419701500602 ↗
37. A theoretical model to predict plume rise in shaft generated by growing compartment fire10.1016/j.ijheatmasstransfer.2010.10.012 ↗