journal article·2009-04

Experimental study of fire growth in a reduced-scale compartment under different approaching external wind conditions

Hong Huang, Ryozo Ooka, Naian Liu, Linhe Zhang, Zhihua Deng, Shinsuke Kato

Fire Safety Journal· Volume 44· Issue 3
Publisher page

Abstract

In order to clarify the fire growth process in compartments under external wind conditions, detailed fire tunnel experiments were conducted in a reduced-scale compartment. The approaching external wind velocity was set to 0.0, 1.5 and 3.0 m/s, and the location of the fire source was changed between the downwind corner, upwind corner and center of the compartment. The experiments considered the effect of wind on a through-ventilation situation. The temperatures of the air and the wall surfaces in the compartment and the temperatures of the flames ejected from the opening were measured. The fuel mass loss rate and the heat flux from the opening were also recorded. Different fire growth characteristics are shown under different wind and fire source conditions. The temperature rises faster and burnout time is reduced under windy conditions. It is found that external wind has two opposing effects. One is to promote combustion within the compartment and thus raise the temperature, the other is to blow away and dilute the combustible gases in the compartment and decrease the temperature, or hasten its extinction. When the approaching wind velocity is high, the external plume is greatly inclined to the downwind side, and the flame becomes larger, thus increasing the risk of the fire spreading to neighboring buildings. The dimensionless temperature of the external flame was a little lower than the results indicated by Yokoi's experiments without wind.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (16)

Show source-provided references
1. Drysdale · 1998
2. Major fire disasters involving flashover10.1016/0379-7112(91)90030-3 ↗
3. Estimating temperatures in compartment fires
4. S. Yokoi, Study on the prevention of fire-spread caused by hot upward current, Report of the Building Research Institute No. 34, 1960.
5. P.H. Thomas, M. Law, The projection of flames from burning buildings, Fire Research Note No. 921, 1972.
6. Tanaka · 1993
7. M.L. Bullen, P.H. Thomas, Compartment fires with non-cellulose fuels, Seventeenth Symposium (International) on Combustion, The Combustion Institute, Pittsburgh, 1979, pp. 1139–1148.10.1016/S0082-0784(79)80108-3 ↗
8. Properties of external flame taking into consideration excess fuel gas ejected from fire compartment10.3130/aija.66.1_7 ↗
9. Temperature profiles of window jet plume10.3210/fst.24.17 ↗
10. Y. Takahashi, Y. Hayashi, N. Kodama, Y. Omiya, An experimental study on compartment fire affected by external wind, Summaries of Technical Papers of the Annual Meeting of Architectural Institute of Japan, 2006, pp. 241–244 (in Japanese).
11. K. Kawagoe, T. Sekine, Estimation of temperature–time curves in rooms, Occasional Report No. 11, Building Research Institute, Tokyo, 1963.
12. P.H. Thomas, A.J.M. Heselden, M. Law, Fully developed compartment fires: two kinds of behavior, Fire Research Technical Paper No. 18, HMSO, London, 1967.
13. Nonlinear behavior of enclosure fires
14. Incident heat flux to fuel and burning rate in ventilation-controlled fires10.3130/aijs.60.169_1 ↗
15. O. Sugawa, H. Satoh, Y. Oka, Flame height from rectangular fire sources considering mixing factors, in: Proceedings of the Third International Symposium on Fire, International Association of Fire Safety and Science, 1991, pp. 435–444.10.3801/IAFSS.FSS.3-435 ↗
16. Theoretical approach on flame tilt based on apparent flame height in free boundaries10.3130/aijs.64.147_3 ↗