journal article·2009-08

Unexposed-face temperature criteria in fire resistance tests: A reappraisal

Vytenis Babrauskas

Fire Safety Journal· Volume 44· Issue 6
Publisher page

Abstract

Abstract Fire resistance tests for barriers, e.g., walls or floor/ceiling assemblies, utilize unexposed-face temperature criteria as one of the means of determining whether the specimen passes the test. The purpose of a temperature limit on the unexposed face is to prevent fire propagation which might occur by igniting adjacent combustibles in the space not yet fire-involved. The actual criteria date to 1918, with only trivial changes have been made subsequently. Knowledge gained in the intervening decades allows a much more realistic assessment of the potential for ignition. The current literature has been reviewed and the results indicate that the criteria used is excessively conservative. A recommendation is made that 400 °C represents a conservative bound to experimental data on all materials which could see potential use in any facilities that are not dedicated to the storage of hazardous goods (the existing fire-resistance standards are not intended for the protection of hazardous-goods occupancies, in any case). The 400 °C is a fixed value and not a temperature-rise value. Under the existing system, the criteria were two-fold: a limit on the average temperature rise, and a limit on the single-point (worst case) temperature rise. Since the values traditionally used were excessively conservative, the higher single-point limit at least served the function of making the entire criterion somewhat less excessive. This will not be needed if a criterion value is adopted which is more consistent with valid experimental data. Thus, it is recommended that a 400 °C temperature limit be adopted, applicable to any thermocouple location, and that a second, average value not be utilized. The review also indicates that the technique for making the unexposed-face measurement, i.e., the thermocouple+pad assembly, is better conceived in the ISO 834 test, thus it is recommended that this same technique be adopted in ASTM E 119.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Fire effects on concrete materials · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (23)

Show source-provided references
1. V. Babrauskas, Fire endurance in buildings, Ph.D. dissertation, Univ. California, Berkeley, 1976.
2. V. Babrauskas, R.B. Williamson, The historical basis of fire resistance testing, Fire Technology Part I 14 (1978) 184–194, 205; Part II (1978) 304–316.10.1007/BF01983053 ↗
3. Standard test methods for fire tests of building construction and materials (ASTM E 119), ASTM Intl., West Conshohocken, PA.
4. Tests on the inflammability of untreated wood and of wood treated with fire-retarding compounds
5. Fire resistance of hollow load-bearing wall tile (Research paper 37)10.6028/jres.002.003 ↗
6. Ignition of wood: a review of the state of the art10.1177/10423910260620482 ↗
7. Babrauskas · 2003
8. Standard test method for determining ignition temperature of plastics (ASTM D 1929), American Society for Testing and Materials, West Conshohocken, PA.
9. Ingberg · 1954
10. 2006
11. Investigating the unexposed surface temperature criteria of standard ASTM E 11910.1007/BF01039972 ↗
12. A method and apparatus for determining the ignition characteristics of plastics
13. Flammability of fabrics and other materials in oxygen-enriched atmospheres. Part I. Ignition temperatures and flame spread rates10.1007/BF02591517 ↗
14. Flammability of fibers, fabrics, and garments
15. Some thoughts and information on nonflammable products
16. Temperature of instantaneous ignition10.1002/fam.810040310 ↗
17. Ignition points of plastic materials
18. Walke · 2005
19. Johnson · 2007
20. Standard test method for fire tests of through-penetration fire stops (ASTM E 814), ASTM Intl., West Conshohocken, PA.
21. Fire Resistance Tests—Elements of Building Construction (ISO 834), first ed., International Organization for Standardization, Geneva, 1975.
22. Fire-Resistance Tests—Elements of Building Construction—Part 1: General Requirements (ISO 834-1), International Organization for Standardization, Geneva, 1999.
23. Rodak · 1967