journal article·2017-10

Dimensionless analytical solutions for steady-state fire smoke spread through high-rise shaft

Dahai Qi, Liangzhu (Leon) Wang, Jie Ji, Man Li

Publisher page

Abstract

Abstract Analytical solutions in terms of dimensionless numbers for the smoke spread through high-rise shafts during fires are essential to provide a fundamental understanding of smoke transport physics, which is a complex coupled heat and mass transfer problem. Existing solutions are often dimensional based on simplification of the problem such as assuming adiabatic conditions. In order to obtain the dimensionless analytical solutions, energy balance equation, mechanical energy equation and mass balance equation were established for smoke spread in high-rise buildings under both mechanical and natural venting conditions. Experiments were designed and conducted on two scaled shafts with different sizes and materials, and the measured results were compared to the dimensionless analytical solutions. It was found that the dimensionless analytical solutions could predict temperature profiles, mass flow rate and neutral plane level accurately. The effect of the adiabatic assumption on the accuracy was also discussed. For example, due to the adiabatic assumption, the error of the calculated mass flow rate required during mechanical venting to maintain a high-rise shaft smoke free was found to increase with a dimensionless number, ω , defined by the geometrical and thermal properties of the shaft.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (25)

Show source-provided references
1. Tamura · 1994
2. 2016
3. Chappell · 2016
4. Fire conditions for smoke toxicity measurement10.1002/fam.810180306 ↗
5. Pressurization systems do not work & present a risk to life safety, Case Stud
6. Stairwell smoke control by ventilation
7. Transport characteristics of thermal plume driven by turbulent mixing in stairwell10.1016/j.ijthermalsci.2014.11.009 ↗
8. Experimental investigation on the characteristics of buoyant plume movement in a stairwell with multiple openings10.1016/j.enbuild.2013.09.028 ↗
9. Experimental investigation on the rising characteristics of the fire-induced buoyant plume in stairwells10.1016/j.ijheatmasstransfer.2013.04.030 ↗
10. Influence of staircase ventilation state on the airflow and heat transfer of the heated room on the middle floor of high rise building10.1016/j.apenergy.2013.12.055 ↗
11. Fire drainage system10.1007/BF01038364 ↗
12. An analytical model of heat and mass transfer through non-adiabatic high-rise shafts during fires10.1016/j.ijheatmasstransfer.2014.01.042 ↗
13. A hand calculation method of smoke movement through high-rise building shaft
14. The effects of non-uniform temperature distribution on neutral plane level in non-adiabatic high-rise shafts during fires10.1007/s10694-015-0554-2 ↗
15. Studies on smoke movement in stairwell induced by an adjacent compartment fire10.1016/j.applthermaleng.2009.01.009 ↗
16. Experimental and numerical study of buoyancy-driven stairwell ow in a three storey building10.1016/S0360-1323(01)00060-9 ↗
17. Experimental study on evacuation process in a stairwell of a high-rise building10.1016/j.buildenv.2011.07.009 ↗
18. Dols · 2015
19. Numerical simulation of fire-induced flow through a stairwell10.1016/j.buildenv.2004.07.011 ↗
20. A new model for determining neutral-plane position in shaft space of a building under fire situation10.1016/j.buildenv.2007.02.004 ↗
21. An experimental study of smoke movement in multi-storey buildings10.1007/s10694-009-0132-6 ↗
22. Comparison of FDS prediction of smoke movement in a 10-Storey building with experimental data10.1007/s10694-008-0075-3 ↗
23. Klote · 1991
24. Klote · 2012
25. Analytical models for evaluating buoyancy-driven ventilation due to stack effect in a shaft considering heat transfer from shaft interior boundaries10.1007/s11771-012-1052-z ↗