journal article·2010-09

Investigation of pitting corrosion of a copper tube in a heating system

Seung-Hwan Lee, Jung-Gu Kim, Ja-Young Koo

Engineering Failure Analysis· Volume 17· Issue 6
Publisher page

Abstract

Abstract Electrochemical tests, as well as surface and chemical analyses were used to examine the mechanism of pitting failure of a copper tube. Synthetic tap water simulating the hot water in a heating system and field-used heating water at 60 °C were used as electrolytes in these tests. The results showed that the presence of a Cu(I) oxide layer on the copper surface is essential for pitting corrosion of a copper tube in hot synthetic tap water. Moreover, the pitting corrosion of copper tubes is preferred in heating water containing higher concentrations of Fe species and under stagnant condition.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Corrosion Behavior and Inhibition · Concrete Corrosion and Durability · Hydrogen embrittlement and corrosion behaviors in metals

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (10)

Show source-provided references
1. Corrosion behavior of annealed and hard-drawn copper in soft tap water10.5006/1.3293614 ↗
2. Type I pitting of copper tubes from a water distribution system10.1016/S1350-6307(97)00029-0 ↗
3. The pitting corrosion of copper10.1002/j.1551-8833.1994.tb06226.x ↗
4. General corrosion of copper in domestic drinking water installations: scientific background and mechanistic understanding10.1179/174327806X94009 ↗
5. The assessment of short term data of pipe corrosion in drinking water-II. Copper10.1016/0010-938X(93)90034-E ↗
6. Corrosion mechanisms and products of copper in aqueous solutions at various pH values10.5006/1.3280482 ↗
7. Jones · 1996
8. The copper tube handbook. Copper Development Association Inc., NY 10016, New York: 2006. p. 10–8. Available at: www.copper.org.
9. Corrosion of flue gas desulfurization systems
10. Crum JR, Shoemmaker, Stiltner G. The role of nickel alloys in fighting corrosion in wet limestone FGD systems, Corrosion 96; Paper No. 454.