Performance of a VRLA battery in an arctic environment
Source abstract
Abstract
Abstract The successful operation of stationary lead-acid batteries of the VRLA/AGM type at cold and extremely cold temperatures is a precondition for the further expansion of their application envelope. Application oriented tests and investigations show a surprisingly robust behavior of such batteries under temperature conditions as low as −30 °C. The results obtained in these tests are presented and show data concerning available discharge energy at low temperatures, the behavior during charge and discharge cycles, the effect of freeze and thaw cycles and structural aspects of the “frozen” electrolyte at these temperatures.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Advanced Battery Technologies Research · Gas Sensing Nanomaterials and Sensors
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (2)
Show source-provided references
1. G.R.L. Brossard, L.D. Gallop, Technical Note no. 79-15, Defence Research Establishment Ottawa, August 1979.
2. M.L. Eugene, Valeriote, Technical Note no. 79-24, Defence Research Establishment Ottawa, October 1979.