Development and field experience of monitoring system for valve-regulated lead–acid batteries in stationary applications
Source abstract
Abstract
Abstract With ever-evolving information technology, it is becoming increasingly important to secure reliable back-up power supplies in telecommunications networks, data-processing facilities, utilities, etc. While valve-regulated lead–acid (VRLA) batteries are predominantly used nowadays, their diagnosis technology is not fully developed. As partial-discharge techniques require temporarily shutting-down of the system and also degrade battery life, manual testers based on an ohmic techniques have become popular. Accordingly, the Battery Condition Watcher (BCW) has been developed and commercialized. This is an automatic monitoring system with remote communication capabilities. It measures the internal impedance, voltage and temperature of individual cells or batteries with high accuracy. These parameters are subjected to data processing to enable diagnosis of battery conditions and life. Some aspects of field usage of the BCW are reported.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Advanced Battery Technologies Research · IoT-based Smart Home Systems · Embedded Systems and FPGA Design
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (8)
Show source-provided references
1. Kiyokawa · INTELEC · 2000 · 703
2. P. Haring, H. Giess, Ninth European Lead Battery Conference, Berlin, Germany, September 2004, Paper 6.3.
3. Evans · INTELEC · 2004 · 356
4. Jongerius · INTELEC · 2001 · 313
5. Porebski · INTELEC · 2005 · 113
6. Takahashi · INTELEC · 2003 · 664
7. Karlsson · INTELEC · 1999 · 21
8. Okada · INTELEC · 2003 · 373