Microcontroller-based on-line state-of-charge estimator for sealed lead–acid batteries
Source abstract
Abstract
Abstract This paper presents a microcontroller-based, on-line battery state-of-charge (SOC) estimator, and monitoring system for sealed lead–acid batteries, used as back-up power supplies in various applications. The proposed SOC estimation system consists of a combination of the discharge time versus discharge rate data given in manufacturers’ data sheets, and coulometric measurements. Battery SOC monitoring tests have been carried out under both constant and dynamic load conditions, and for alternate charge–discharge cycles of lead–acid batteries of different capacities, and for different operating temperatures. The test results have shown that a very good accuracy in the estimation of available capacity is obtained for various practical operating conditions. Changes in battery characteristics which occur due to ageing are also taken into account by estimating the actual capacity of the battery, and adopting the corresponding recharacterization of the aged lead–acid cells.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Advanced Battery Technologies Research · Sensor Technology and Measurement Systems · Wireless Sensor Networks for Data Analysis
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (12)
Show source-provided references
1. D. Linden, Handbook of Batteries, McGraw-Hill, New York, 1995.
2. J.P. Cun, J.N. Fiorina, M. Fraisse, H. Mabboux, The experience of a UPS company in advanced battery monitoring, Intelec’96, Boston, US, 1996, pp. 22–25.
3. I. Kurisawa, M. Iwata, Internal resistance and deterioration of VRLA battery—analysis of internal resistance obtained by direct current measurement and its application to VRLA battery monitoring technique’, Intelec’97, Melbourne, Australia, 1997, pp. 29–33.
4. R.V. Biagetti, A.M. Pesco, Apparatus and method for adaptively predicting battery discharge reserve time, US Patent 4 952 862 (1989).
5. T. Hubert, A battery system using adaptive run-time estimation, software controlled multi-mode charging and intrinsic diagnostics combined to enhance UPS reliability’, in: Proceedings of the HFPC’95, pp. 382–395.
6. Determination of lead–acid battery capacity via mathematical modeling techniques10.1109/60.148564 ↗
7. VRLA battery state of charge estimation in telecommunication power systems10.1109/41.847897 ↗
8. M. Kozaki, T. Yamazaki, Remaining battery capacity meter and method for computing remaining capacity, US Patent 5 691 078 (1997).
9. A battery state-of-charge indicator for electric wheelchairs10.1109/41.161471 ↗
10. Methods for state of charge determination and their applications10.1016/S0378-7753(01)00560-2 ↗
11. Non-intrusive measurement of the state-of-charge of lead–acid batteries using wire-wound coils10.1016/S0378-7753(01)00852-7 ↗
12. Using optical absorption to measure state of charge of lead acid batteries10.1117/1.601999 ↗