journal article·2000-10

Influence of air flow velocity distribution on current interruption in flat-type arc quenching chamber

T. Matsumura, Y. Yokomizu, H. Ohno

Vacuum· Volume 59· Issue 1
Publisher page

Abstract

Abstract Current interrupting capability and distribution of the airflow velocity were investigated in a flat-type air-blast arc quenching chamber. Seven orifice-nozzles with different inlet widths were used to obtain various distributions of the flow velocities. A number of interruption tests for an AC current with a peak value of 1000 A revealed that a decrease in the inlet width from 20 to 10 mm markedly raises the failure rate of the arc interruption from 40 to 97% and that raising the inlet width from 20 to 34 mm gradually increases the failure rate from 40 to 66%. Calculation results of airflow velocity distributions in the absence of the arc lead us to find out the correlation that less uniform distribution or wider generation region of the vortex increases the failure rate of the arc interruption.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Electrical Fault Detection and Protection · Vacuum and Plasma Arcs · Welding Techniques and Residual Stresses

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (12)

Show source-provided references
1. Current zero behaviour of an SF6 gas-blast arc
2. Study of a circuit-breaker arc with self-genetated flow10.1109/27.62361 ↗
3. Morita T, Miyachi I. Classification of interrupting characteristics by thermal arc model. Proceedings of the Eighth International Conference on Gas Discharges and their Applications, Oxford, 1985. p. 73.
4. Dielectric recovery of an air blast monoflow model interrupter with insulating nozzle10.1109/TPWRD.1986.4307983 ↗
5. Analytical prediction of transient breakdown characteristics of SF6 gas circuit breaker10.1109/61.32666 ↗
6. Investigation of technology for developing large capacity and compact size GCB10.1109/61.584361 ↗
7. Garzon RD. High voltage circuit breakers: design and applications. New York: Marcel Dekker, 1996. p. 141–4.
8. Kito Y, Ohno H. Electron density measurement by sensitive cut-off attribute of incident EHF microwave in a transient narrow gap arc. Proceedings of the Seventh International Conference on Gas Discharges and their Applications. 1982. p. 529.
9. Ohno H, Naganawa H, Matsumura T, Kito Y. Effects of nozzle shapes on electron density distribution along the axis and on arc interruption capability observed in flat-type air-blast quenching chamber. Proceedings of the Ninth International Conference on Gas Discharges and their Applications, Venezia, 1988. p. 47.10.1541/ieejpes1972.108.423 ↗
10. A novel approach to ac air arc interruption phenomena viewed from the electron density at current zero10.1088/0022-3727/22/1/018 ↗
11. Tanishita I. Heat transfer engineering. Tokyo: Shokabo, 1986. p. 310 (in Japanese).
12. Boulos MI, Fauchais P, Pfender E. Thermal plasmas — fundamental and applications. New York: Plenum Press, 1994. p. 413–5.10.1007/978-1-4899-1337-1 ↗