Current interruption capability of H2–air hybrid model circuit breaker
Source abstract
Abstract
Abstract We have proposed a hybrid circuit breaker (CB) consisting of two series-connected arc devices with different arc-quenching media employing non-greenhouse gases. In the present research, a model hybrid CB adopting H 2 and air as the quenching gases was constructed to examine the current interrupting performance. The model hybrid CB successfully interrupted an ac current with a peak value of 950 A. This interrupting capability was proved to be higher than that for another model CB being composed of two series-connected air arc switches.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Vacuum and Plasma Arcs · Electrical Fault Detection and Protection · Silicon Carbide Semiconductor Technologies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (5)
Show source-provided references
1. Garzon RD. High voltage circuit breakers—design and applications. New York: Marcel Dekker; 1997. p. 166.
2. Christophorou · NIST Technical Note · 1997 · 1435 · 2
3. O'connell · Electra · 2001 · 200 · 16
4. Yokomizu · Trans IEE Japan · 2003 · 123-B · 450
5. Matsumura T, et al. 2002 National Conventional Record, IEE Japan, 2002. p. 6–163.