Safe stroke of vacuum breaking process in DC circuit breaker commutated by intermediate frequency current
Source abstract
Abstract
Abstract The safe stroke between contacts of vacuum switch is the key parameter that can withstand transient recovery voltage (TRV) after arc extinction. In order to determine the minimum safe stroke during direct current (DC) interruption, this paper starts with the characteristic analysis of the commutation process. After breaking current zero crossing, contact gap is used to correlate the dielectric recovery level with TRV. In terms of theoretical description, based on the sheath development analysis of continuous transition model (CTM), different commutation moments and frequency have a perceptible effect on the TRV and dielectric recovery process. The breaking test of DC synthesis circuit with dual power supply is used to further verify the dielectric recovery level of vacuum gap, and the minimum safe stroke corresponding to reliable interruption. Simulation and experimental results show that safe stroke increases with the higher breaking current, TRV and its change rate during the DC breaking process, the corresponding commutation moment should be delayed. Finally, the influence of arc appearance on the safe stroke is discussed by analyzing the arc image of the draw-arc process. The safe stroke is helpful to determine the time setting for commutation moment and reliable breaking process of DC vacuum circuit breaker.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Electrical Fault Detection and Protection · Vacuum and Plasma Arcs · HVDC Systems and Fault Protection
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (28)
Show source-provided references
1. HVDC Circuit Breakers: a review identifying future research needs10.1109/TPWRD.2010.2095889 ↗
2. R&D and application of advanced power transmission technology in China
3. High voltage level vacuum switching technology
4. Investigation on the HVDC vacuum circuit breaker based on intelligent models
5. A DC vacuum circuit breaker based on electromagnetic repulsion actuator
6. Effect of magnetic field on different opening processes of multi-break vacuum gaps10.1109/ACCESS.2021.3053347 ↗
7. Wang · 1993
8. Slade · 2008
9. Design and experimental of 126kV vacuum circuit breaker based on fiber-controlled vacuum interrupter modules in series
10. Sheath growth in a low pressure plasma
11. Vacuum circuit breaker current-zero phenomena10.1109/TPS.2005.856486 ↗
12. Influence of contact distance on the appearance of vacuum arcs with different AMF contacts10.1109/TPS.2005.856508 ↗
13. Current zero behavior of vacuum interrupters with bipolar and quadrupolar AMF contacts10.1109/TPS.2003.818453 ↗
14. The short vacuum-arc . I. Experimental investigations10.1109/27.3840 ↗
15. Transition to the diffuse mode for high-current drawn arcs in vacuum with an axial magnetic field10.1109/TPS.2003.818416 ↗
16. Transition mode of the vacuum arc in an axial magnetic field: comparison of experimental results and theory10.1109/TPS.2005.856505 ↗
17. A relationship between minimum arcing interrupting capability and opening velocity of vacuum interrupters in short-circuit current interruption10.1109/TPWRD.2018.2838344 ↗
18. Influence of the contact opening speed on DC vacuum arc10.1109/TPS.2015.2390256 ↗
19. Recovery of dielectric strength after DC interruption in vacuum10.1109/TDEI.2015.005167 ↗
20. Characteristics and influencing factors of the post-arc current in vacuum DC interruption10.1109/TPS.2017.2774450 ↗
21. Experimental research on the safe stroke of HVDC vacuum circuit breaker
22. Research on commutation parameters of mechanical HVDC vacuum circuit breaker
23. Synchronous control of module series connection interruption in 110 kV DC vacuum circuit Breaker
24. Current interruption ability of vacuum switches
25. Synthetic testing method with three power sources for HVDC interruption
26. Interruption characteristics of hybrid dc vacuum circuit breakers with small contact gaps
27. An investigation on dielectric strength recovery of a vacuum switch
28. Study on the variation of the arc area in vacuum DC interruption10.1016/j.vacuum.2018.08.006 ↗