Measurement and modelling of Very Fast Transient Current in 220 kV GIS
Source abstract
Abstract
Abstract This paper focus on measurement and modelling of Very Fast Transient Current (VFTC). Experiments are carried out on a real sized 220 kV class Gas Insulated Switchgear (GIS). A rogowski coil along with a set of optical fiber transmission system is used to measure VFTCs. The experimental results shows that the upper cutoff frequency of VFTC can be up to dozens of MHz and the amplitude of the VFTC can be up to several kA. An improved Toepler model is built and the values of parameters in it is calculated from experimental waveforms. The simulation results can coincide well with the experimental ones.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Thermal Analysis in Power Transmission · Lightning and Electromagnetic Phenomena · Power Systems Fault Detection
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (9)
Show source-provided references
1. Lu · 2005 · 5
2. Modelling and analysis guidelines for very fast transients10.1109/61.544291 ↗
3. Arc resistance of laser-triggered spark gaps10.1063/1.336023 ↗
4. Zur Kenntnis der Gesetze der Gleitfunkenbildung10.1002/andp.19063261202 ↗
5. Resistance and inductance of a gas arc
6. Resistance of a xenon plasma in a large flash lamp
7. Über das Toeplersche Funkengesetz10.1007/BF01330625 ↗
8. The resistance of Sparks10.1063/1.1661429 ↗
9. Capacitive sensor for the measurement of VFTO in GIS