journal article·2024-08

A Novel Methodology for the Transformer Winding Equivalent Ladder Network Circuit Parameters Identification by Employing the Frequency-Domain and Population Based Method

Abdallah Chanane, Hamza Houassine

Publisher page

Abstract

Abstract Frequency response analysis (FRA) is the widely used technique for diagnosis of power transformer winding. Previous works in the field of FRA have steer to the standardization of its measurements procedure. To date, there is no reliable standard code for the interpretation of FRA results. In this context, this paper proposes a new parametric method to synthesis the High frequency electrical ladder network circuit (HF-ELNC) of the transformer winding. Initially, a nondestructive process is applied to extract three main winding parameters. Mainly, the shunt-series capacitances and the total equivalent inductance basing on the frequency response data from the winding terminal. To this end, the proposed continuous-time state–space model is converted into a gain-numerator-denominator form. After that, the derived matrix equations are iteratively estimated by population-based algorithm using enhanced logistic choatic marine predator algorithm (ELCMPA), from where, three objective functions are considered in the model of identification including the capacitances, the inductances and the resistances. As well, classical methods such as finite elements or analytical formulas require design winding specifications. In this study, instead of winding geometry knowledge, the proposed method certifies a unique, physically and mutually coupled HF-ELNC. The accuracy of the proposed method is validated through case study of a real transformer winding.
Source: openalex_inverted_index · Quality: baseline

Research context

OpenAlex topics: Power Transformer Diagnostics and Insulation · Magnetic Properties and Applications · Power Quality and Harmonics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (45)

Show source-provided references
1. Venikar, P.A., Ballal, M.S., Umre, B.S., and Suryawanshi, H.M., A novel offline to online approach to detect transformer interturn fault, IEEE Trans. Power Deliv., 2015, vol. 31, No. 2, pp. 482–492.10.1109/TPWRD.2015.2440448 ↗
2. Masoum, A.S., Hashemnia, N., Abu-Siada, A., Masoum, M.A.S., and Islam, S.M., Online transformer internal fault detection based on instantaneous voltage and current measurements considering impact of harmonics, IEEE Trans. Power Deliv., 2014, vol. 32, no. 2, pp. 587–598.10.1109/TPWRD.2014.2358072 ↗
3. Hong, K.H. and Zhang, Z.J., Winding condition assessment of power transformers based on vibration correlation, IEEE Trans. Power Deliv., 2014, vol. 30 (4), pp. 1735–1742.10.1109/TPWRD.2014.2376033 ↗
4. Seo, J.M. and Kim, S.T., A joint vibration and arcing measurement system for online condition monitoring of on-load tap changer of the power transformer, IEEE Trans. Power Deliv., 2016, vol. 32 (2), pp. 1031–1038.10.1109/TPWRD.2016.2531186 ↗
5. Hashemnia, N., Abu-Siada, A., and Islam, S., Detection of power transformer bushing faults and oil degradation using frequency response analysis, IEEE Trans. Dielectr. Electr. Insul., 2016, vol. 23 (1), pp. 222–229.10.1109/TDEI.2015.005032 ↗
6. Tahir, M.T.S. and Sadaf, M.S., Analysis of statistical methods for assessment of power transformer frequency response measurements, IEEE Trans. Power Deliv., 2020, vol. 36 (2), pp. 618–626.10.1109/TPWRD.2020.2987205 ↗
7. Khalid H. Ibrahim, Nourhan R. Korany, and Saber M. Saleh, Effects of power transformer high-frequency equivalent circuit parameters non-uniformity on fault diagnosis using SFRA test, Ain Shams Eng. J., 2022, vol. 13 (4), p. 101674.10.1016/j.asej.2021.101674 ↗
8. Reddy, R.S.K. and Kumar, K.M., Performance evaluation of laboratory and industrial equipment in FRA measurement, Iran. J. Sci. Technol. Trans. Electrical Eng., 2024, vol. 48 (1), pp. 187–199.10.1007/s40998-023-00650-5 ↗
9. IEEE guide for the application and interpretation of frequency response analysis for oil-immersed transformers, in IEEE Standard for General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers, 2013.
10. IEC Std. IEC60076-18. Measurement of frequency response, 2012.
11. Patrick Picher, Stefan Tenbohlen, Mark Lachman, Alaor Scardazzi, and Poorvi Patel, Current state of transformer FRA interpretation, Procedia Eng., 2017, vol. 202, pp. 3–12.10.1016/j.proeng.2017.09.689 ↗
12. Bigdeli, M.A.D. and Gholamipour, B. Detection of probability of occurrence, type, and severity of faults in transformer using frequency response analysis based numerical indices, Measurement, 2021, vol. 168, pp. 108–322.10.1016/j.measurement.2020.108322 ↗
13. Zhao, Z.T.C., Chen, C.Y., Zhang, Q., and Yang, C., Interpretation of transformer winding deformation fault by the spectral clustering of FRA signature, Int. J. Electr. Power Energy Syst., 2021, vol. 130, p. 106933.10.1016/j.ijepes.2021.106933 ↗
14. Zhang, Z., Characterizing transformer HV–LV winding FRA curves through derivation of transfer functions from FRA data, Electr. Power Syst. Res., 2024, vol. 228, p. 110055.10.1016/j.epsr.2023.110055 ↗
15. Ragavan, K. and Lakshmanan, S., Localization of changes in a model winding based on terminal measurements: Experimental study, IEEE Trans. Power Deliv., 2007, vol. 22 (3), pp. 1557–1565.10.1109/TPWRD.2006.886789 ↗
16. Prasanna, K.L.S.M. and Muralidhar, M., Terminal measurements-based series capacitance estimation of power transformer windings using frequency domain subspace identification, IEEE Trans. Instrum. Meas., 2023, vol. 72, p. 1503409.10.1109/TIM.2023.3311074 ↗
17. Chanane, A., Bouchhida, O., and Houassine, H., Investigation of the transformer winding high-frequency parameters identification using particle swarm optimization method, IET Electr. Power Appl., 2016, vol. 10 (9), pp. 923–931. https://doi.org/10.1049/iet-epa.2016.007410.1049/iet-epa.2016.0074 ↗
18. Chanane, A., Belazzoug, M., and Houassine, H., A new procedure for high-frequency decentralized modeling parameters identification of a transformer winding construction using frequency response analysis based on logistic chaotic JAYA algorithm, Russ. J. Nondestr. Test., 2023, vol. 59(4), pp. 456–467.10.1134/S1061830923600041 ↗
19. Biswas, B. and Satish, L., Experimental results on estimation of effective inductance associated with winding resonances of 1-Φ and 3-Φ transformers using measured FRA, IEEE Trans. Power Deliv., 2020, vol. 35 (5), pp. 2378–2386.10.1109/TPWRD.2020.2967092 ↗
20. Mukherjee, P. and Satish, L., Estimating the equivalent air-cored inductance of transformer winding from measured FRA, IEEE Trans. Power Deliv., 2017, vol. 33(4), pp. 1620–1627.10.1109/TPWRD.2017.2735627 ↗
21. Biswas, B. and Satish, L., Analytical expressions to link SCNF and OCNF of transformer windings to their inductances and capacitances for 1-Φ, 3-ΦY and Δ configurations, IEEE Trans. Power Deliv., 2019, vol. 34(4), pp. 1725–1735.10.1109/TPWRD.2019.2918811 ↗
22. Toudji, M., Parent, G., Duchesne, S., and Dular, P., Determination of winding lumped parameter equivalent circuit by means of finite element method, IEEE Trans. Magn., 2017, vol. 53 (6), pp. 1–4.10.1109/TMAG.2017.2671423 ↗
23. Xiaozhen Zhao, Chenguo Yao, Ahmed Abu-Siada, and Ruijin Liao, High-frequency electric circuit modeling for transformer frequency response analysis studies, Int. J. Electr. Power Energy Syst., 2019, vol. 111, pp. 351–368.10.1016/j.ijepes.2019.04.010 ↗
24. Ren Fuqiang, Ji Shengchang, Zhu Lingyu, Zhang Fan, and Liu Yong, Generic algorithm to calculate Jacobian matrix used for ladder network parameters identification and winding fault diagnosis, IET Gener. Transm. Distrib., 2019, vol. 13 (15), pp. 3370–3377.10.1049/iet-gtd.2019.0250 ↗
25. Ragavan, K. and Lakshmanan, S.L., Construction of physically realizable driving-point function from measured frequency response data on a model winding, IEEE Trans. Power Deliv., 2008, vol. 23 (2), pp. 760–767.10.1109/TPWRD.2008.915815 ↗
26. Reddy, R.S.K. and Kumar, K.M., Towards unique circuit synthesis of power transformer winding using gradient and population-based methods, IEEE Latin Am. Trans., 2023, vol. 21 (3), pp. 490–497.10.1109/TLA.2023.10068837 ↗
27. Chanane, A., Houassine, H., and Bouchhida, O., Enhanced modeling of the transformer winding high-frequency parameters identification from measured frequency response analysis, IET Gener. Transm. Distrib., 2019, vol. 13 (8), pp. 1339–1345.10.1049/iet-gtd.2018.5514 ↗
28. Mukherjee, P. and Satish, L., Construction of equivalent circuit of a single and isolated transformer winding from FRA data using the ABC algorithm, IEEE Trans. Power Deliv., 2012, vol. 27 (2), pp. 963–970.10.1109/TPWRD.2011.2176966 ↗
29. Shintemirov, A., Tang, W.J., Tang, W.H., and Wu, Q.H., Improved modeling of power transformer winding using bacterial swarming algorithm and frequency response analysis, Electr. Power Syst. Res., 2010, vol. 80 (9), pp. 1111–1120.10.1016/j.epsr.2010.03.001 ↗
30. Mehdi Bigdeli and Ahmed Abu-Siada, Clustering of transformer condition using frequency response analysis based on k-means and GOA, Electr. Power Syst. Res., 2022, vol. 202, p. 107619.10.1016/j.epsr.2021.107619 ↗
31. Chaouche Moustafa Sahnoune, Houassine Hamza, Moulahoum Samir, and Colak Ilhami, BA to construction of equivalent circuit of a transformer winding from frequency response analysis measurement, IET Electr. Power Appl., 2018, vol. 12 (5), pp. 728–736.10.1049/iet-epa.2017.0418 ↗
32. Pramanik, S. and Satish, L., Estimation of series capacitance of a transformer winding based on frequency-response data: An indirect measurement approach, IEEE Trans. Power Deliv., 2011, vol. 26(4), pp. 2870–2878.10.1109/TPWRD.2011.2167247 ↗
33. Pramanik, S. and Satish, L., Estimation of series capacitance for a three-phase transformer winding from its measured frequency response, IEEE Trans. Power Deliv., 2013, vol. 28 (4), pp. 2437–2444.10.1109/TPWRD.2013.2260772 ↗
34. Pramanik, S. and Satish, L., Time-domain approach to estimate series capacitance of an isolated phase winding of a transformer, IEEE Trans. Power Deliv., 2014, vol. 24 (9), pp. 1939–1945.10.1109/TPWRD.2014.2305763 ↗
35. Muhammed, A.S.L. and Ushanov, K., Elegant procedure to estimate series capacitance of a uniform transformer winding from its measured FRA: Implementable on existing FRA instruments, IET High Volt., 2020, vol. 5 (4), pp. 444–453.10.1049/hve.2019.0251 ↗
36. De, S.D.A. and Biswas, G.D., Self-capacitance grading approach to suppress winding resonance in EHV transformers under oscillatory terminal disturbances, IET High Volt., 2018, vol. 3 (4), pp. 310–315.10.1049/hve.2018.5028 ↗
37. Suassuna de Andrade Ferreira, Regelii Picher, Patrick Meghnefi, Fethi Fofana, Issouf Ezzaidi, Hassan Volat, and Christophe Behjat, Reproducing transformers’ frequency response from finite element method (FEM) simulation and parameters optimization, Energies, 2023, vol. 16 (11), p. 43.
38. F. Ren, Kang, Z., Ji, S., and Li, Q., High-frequency ladder network synthesis of transformer winding for its mechanical condition assessment, IEEE Trans. Ind. Electron., 2022, vol. 70 (6), pp. 6261–6271.10.1109/TIE.2022.3194568 ↗
39. Zhang, Z., Derivation of transformer winding equivalent circuit by employing the transfer function obtained from frequency response analysis data, IET Electr. Power Appl., 2024, vol. 18, no. 7, pp. 826–840.10.1049/elp2.12436 ↗
40. Zhang, Z., Characterizing transformer HV–LV winding FRA curves through derivation of transfer functions from FRA data, Electr. Power Syst. Res., 2024, vol. 228, p. 110055.10.1016/j.epsr.2023.110055 ↗
41. Mitra, S.P. and Satish, L., Parametric evaluation to determine type and severity of mechanical fault in transformer winding using frequency response measurement, IEEE Trans. Instrum. Meas., 2024.10.1109/TIM.2024.3382746 ↗
42. Rao Tirlingi, Mitra Sourav, and Pramanik Saurav, A novel estimation methodology for multi-resonance equivalent inductance of transformer winding for inter-turn short-circuit fault detection, Electr. Power Syst. Res., 2024, no. 231, p. 110359.10.1016/j.epsr.2024.110359 ↗
43. Aydemir, S.B., Enhanced marine predator algorithm for global optimization and engineering design problems, Adv. Eng. Software, 2023, vol. 184, p. 103517.10.1016/j.advengsoft.2023.103517 ↗
44. Faramarzi Afshin, Heidarinejad Mohammad, Mirjalili Seyedali, and Gandomi Amir, Predators algorithm: A nature-inspired metaheuristic, Expert Syst. Appl., 2023, vol. 152, p. 113377.10.1016/j.eswa.2020.113377 ↗
45. Chanane, A. and Houassine, H., Toward unique electrical ladder network model synthesis of a transformer winding high-frequency modeling using K-means and metaheuristic-based method, COMPEL Int. J. Comput. Math., 2024.10.1108/COMPEL-05-2023-0207 ↗