Assessment of the Fire Hazard Presented by a Burning Pool of Toluene Diisocyanate (TDI)
Source abstract
Abstract
Fire tests have been conducted with TDI under conditions simulating a pool fire originating, e.g. from a leakage of stored TDI. The facilities of Cerchar * provide conditions of a free-burning, well-ventilated fire. Burning rate, heat and smoke development and toxic gas emission were determined as a function of the pool diameter up to 1 m 2 . Results are compared with small scale test results. Burning rate increases with increasing pool diameter reaching 2 kg/m2-min at 1 m 2 area. Yields of permanent gases do not differ significantly with increasing pool area, with HCN amounting to 5 mg/g. Free TDI is found in fire gas up to 15 ppm corresponding to a yield of 7 mg/g.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Environmental and Industrial Safety
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Ineris, Verneuil-in-Halatte, France
BASF Aktiengesellschaft, Carl Bosch Strasse 38, WD-6700, Germany
References
Reference metadata was not supplied for this record.