journal article·1994-05

Validation of a Zone Model for Predicting Smoke Obscuration in Rooms

Pravinray D. Gandhi

Journal of Fire Sciences· Volume 12· Issue 3
Publisher page

Abstract

Fires in a room often start small with the ignition of a combusti ble item such as a waste paper basket. As the fire grows, a smoke layer develops at the ceiling level. The smoke, as it descends, obscures signs and egress routes thus making it difficult to escape from the fire-affected room. In this paper, a brief discussion is given on the measurement of smoke and the importance of various smoke measurement parameters and the differential equations for calculating the smoke obscurations in a room are presented. The predictions of the model are then compared with obscuration data available from room corner fire tests involving three type of wall lining materials. The comparisons are in reasonable agreements with the test data. Some loss of smoke information is observed for polystyrene foam material and this resulted in the model under predicting the smoke obscuration as compared to the fire test. This loss of infor mation is suspected to be due to deposition of the soot on the duct surfaces dur ing the transport process.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Wind and Air Flow Studies · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Senior Staff Engineer Underwriters Laboratories Inc. 333 Pfingsten Road Northbrook, IL 60062-2096

References (17)

Show source-provided references
1. Nelson, H. · 1973
2. 10.1088/0508-3443/10/9/30910.1088/0508-3443/10/9/309 ↗
3. Seader, J.D. · Fire Research · 1979 · 1 · 3
4. 1990
5. Babrauskas, V. and G. Mulholland. 1987. "Smoke and Soot Data Determinations in the Cone Calorimeter," Mathematical Modeling of Fire, ASTM STP 983, American Society for Testing and Materials, 1916 Race Street, Philadelphia, PA, U.S.A., pp. 83-104.10.1520/STP26219S ↗
6. Seader, J. and I. Einhorn. 1976. "Some Physical, Chemical, and Toxicological, and Physiological Aspects of Fire Smokes," Sixteenth Symposium (International) on Combustion , The Combustion Institute, Pittsburgh, PA, pp. 1423-1445.10.1016/S0082-0784(77)80426-8 ↗
7. 10.1016/0379-7112(93)90033-M10.1016/0379-7112(93)90033-M ↗
8. Flammability Test Procedure for Seating Furniture for Use in Public Occupancies, Technical Bulletin 133, State of California, Department of Consumer Affairs, Bureau of Home Furnishings and Thermal Insulation, 3485 Orange Grove Avenue, North Highlands, CA 95660.
9. UL1056-Fire Test of Upholstered Furniture, Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL, 60062.
10. UL2043-Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces, Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062.
11. UL1685-Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables, Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL, 60062.
12. 10.1080/0010220840892379410.1080/00102208408923794 ↗
13. McCaffery, B.J. · Combustion and Flames · 1983 · 52
14. Delichatsios, M.A. · 1984
15. 10.6028/NIST.HB.146v210.6028/NIST.HB.146v2 ↗
16. 10.1115/1.324519410.1115/1.3245194 ↗
17. Söderbom, J. 1992. "Smoke Spread Experiments in Large Rooms. Experimental Results and Numerical Simulations," Swedish National Testing and Research Institute, Fire Technology SP Report 1992:52.