Modeling of an ionized electric field on the building near the UHVDC transmission line
Source abstract
Abstract
In this paper, a 3D upstream finite element method is developed to analyze the ionized electric field around the UHVDC transmission lines including the building near it. The ionized electric field around the building is reduced due to the shielding effect of the building and the shielding distance is about three times its height. The ionized electric field including the human body model on the building and away from the building is also taken into account. The ionized electric field distortion ratio of the human body model is discussed in this paper. The distortion ratios for the positions on the building are less than those on the ground.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Aerosol Filtration and Electrostatic Precipitation · High voltage insulation and dielectric phenomena · Lightning and Electromagnetic Phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (16)
Show source-provided references
1. Fu B L. The electric field effect of the HVDC transmission lines on the building nearby (in Chinese). Power System Tech, 1988, 1: 19–25
2. Maruvada P S, Janischewskyj W. Analysis of corona losses on DC transmission lines: I—Unipolar lines. IEEE Trans Power App Syst, 1969, 88: 718–731
3. Maruvada P S, Janischewskyj W. Analysis of corona losses on DC transmission lines. Part II—Bipolar lines. IEEE Trans Power App Syst, 1969, 88: 1476–1491
4. Maruvada P S. Electric field and ion current environment of HVDC transmission lines: Comparison of calculations and measurements. IEEE Trans Power Del, 2012, 27: 401–41010.1109/TPWRD.2011.2172003 ↗
5. Li X B, Cui X, Zhen Y Z, et al. The ionized fields and the ion current on a human model under 800-kV HVDC transmission lines. IEEE Trans Power Del, 2012, 27: 2141–2149
6. Luo Z N, Cui X, Zhang W D, et al. Calculation of the 3-D ionized field under HVDC transmission lines. IEEE Trans Magn, 2011, 47: 1406–140910.1109/TMAG.2010.2090514 ↗
7. Janischewskyj W, Gela G. Finite element solution for electric fields of coronating DC transmission lines. IEEE Trans Power Appl Syst, 1979, 98: 1000–101210.1109/TPAS.1979.319258 ↗
8. Takuma T, Ikeda T, Kawamoto T. Calculation of ion flow fields of HVDC transmission lines by the finite element method. IEEE Trans Power App Syst, 1981, 100: 4802–481010.1109/TPAS.1981.316432 ↗
9. Takuma T, Kawamoto T. A very stable calculation method for ion flow field of HVDC transmission lines. IEEE Trans Power Del, 1987, 2: 189–19810.1109/TPWRD.1987.4308090 ↗
10. Li X. Numerical analysis of ionized fields associated with HVDC transmission lines including effect of wind. Dissertation of Doctoral Degree. Dept Elect Comput Eng, Univ Manitoba, Winnipeg, MB, Canada, 1997
11. Zakariya M, Hamouz A. Corona power loss, electric field, and current density profiles in bundled horizontal and vertical bipolar conductors. IEEE Trans Indus App, 2002, 38: 1182–118910.1109/TIA.2002.802931 ↗
12. Lu T B, Feng H, Cui X, et al. Analysis of the ionized field under HVDC transmission lines in the presence of wind based on upstream finite element method. IEEE Trans Magn, 2010, 46: 2939–294210.1109/TMAG.2010.2044149 ↗
13. Zhen Y Z, Cui X, Luo Z N, et al. FEM for 3D total electric field calculation near HVDC lines (in Chinese). Trans China Electrotech Soc, 2011, 26: 153–160
14. Zhou X X, Lu T B, Cui X, et al. Simulation of ion-flow field at the crossing of HVDC and HVAC transmission lines. IEEE Trans Power Delivery, 2012, 27: 2382–238910.1109/TPWRD.2012.2207409 ↗
15. Sarma M P. Corona Performance of High-voltage Transmission Lines. Baldock: Research Studies Press, 2000
16. Zhao W J. HVDC Engineering Technology (in Chinese). Beijing: China Electric Power Press, 2004