The protective effect of a fire-retardant coating on the insulation failure of PVC cable

Ji Wang, Zhong-Jun Shu, Zhen Chen

Abstract

The failure time of polyvinyl chloride (PVC) insulated power cables was studied using an infrared radiation heating furnace and insulation resistance measurements. The temperature-time curve inside the furnace was similar to that of the ISO 834 standard. Two popular fire protection methods were employed for the cables; one method applied fire-retardant coatings directly on the cable surface, and the other inserted the cables into metal conduits coated with structural steel fire-retardant coating. The results showed that for both protection methods, the failure time of the cable increased with the thickness of the coating. However, if the cable coatings were thicker than 1.5. mm, the coating will crack in the case of cable movement. When the steel structural coating was thinner than 1. mm or thicker than 3. mm, the protective effect was not remarkable for the relatively small expansion multiple. For the longest failure time of the cables, less than 10. min in these tests, neither of the two methods was effective in protecting the electrical cables that supply power (on transmit a signal) to equipment required to operate over a relatively long duration in fire conditions.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Flame retardant materials and properties · Lightning and Electromagnetic Phenomena

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (14)

Show source-provided references
1. Fire duration is a key factor in cable type selection
2. Fire protection of critical circuits-a life and property preserver10.1109/28.703959 ↗
3. Fire-protective and flame-retardant coatings – A state-of-the-art review10.1177/0734904110395469 ↗
4. IEC Standard 332-3. Tests on electric cables under fire conditions. Part 3: Tests on bunched wires or cables, 1987.
5. Ministry of Public Security Standard of CN GA 181-1998. General technical specifications for fire resistive coating of cable, 1998.
6. PrEN 1366-11. Fire resistance tests for service installations – Part 11: Fire protective system for cable systems and associated components; 2010.
7. DIN 4102 Teil 12. Fire behaviour of building materials and building components – Part 12: Circuit integrity maintenance of electric cable systems. Requirements and Testing; 1998.
8. NBN 713-020 add. 3. Fire fighting – Fire performance of building materials and products – Fire resistance of building materials. Add. 3: Electric cables; 1994.
9. EN 50200. Method of test for resistance to fire of unprotected small cables for use in emergency circuits; 2006.
10. EN 50362. Method of test for resistance to fire of lager unprotected power and control cables for use in emergency circuits; 2003.
11. Murphy JE. Determination of failure criteria for electric cables exposed to fire for use in a nuclear power plant risk analysis, a thesis submitted to the faculty of the Worcester Polytechnic Institute; January 2004.
12. Effect of protecting with conduits on insulation failure of ZR-VV cable
13. Fire retardant coatings for electric cables
14. Surface coating and metal-based organic additives-approaches for FRSS PVC cables10.1177/0734904107078676 ↗