Reducing the failures with adding glass insulators to composite insulators of 400 kV transmission line at high altitude

Bora Alboyacı, Mehmet Aytaç Çınar, Yunus Berat Demirol, Mete Uzar

Publisher page

Abstract

Using composite insulators instead of glass insulators in high voltage transmission lines has become common with rapid developments in material technology. This study examined the 270 km long Ispir-Bagistas high voltage line with a 400 kV composite insulator, which was commissioned in 2016. The altitude along the transmission line route varies between 860 and 2800 meters. After the line was commissioned, too many phase-earth failures were experienced. To reduce failures, the Turkish Electricity Transmission Corporation (TEIAS) operator added glass insulators to the existing composite insulators. It was observed that the number of failures decreased significantly after the addition. That study aims to find the most suitable location and the number of glass insulators. Since the design of the insulation system is crucial for network reliability and sustainability, it has become a necessity today to carry out analysis before the design stage. In this context, the pole-insulator systems used in the transmission lines were modelled in the Ansys Electronic Suite finite element analysis program. The influence of the conditions applied in the field was examined. Accordingly, when one, two and three glass insulators are added to the conductor side, the maximum electric field distributions on the composite insulator surface decrease by 19%, 35% and 45%, respectively. In the case of adding glass insulators to the pole side, there is no significant change in the electric field distribution formed on the composite insulator surface. In addition, when adding one, two and three glass insulators, the minimum arc distances increase by approximately 12%, 19% and 21%, respectively. Accordingly, adding three glass insulators to the composite insulator would be appropriate to reduce the failures without changing the composite insulators. Although the electric field decreases up to 45% when glass insulators are added to the conductor side, it would be convenient to add them to the pole side for easy application on the field. Due to the arc distances, it is not recommended that the number of glass insulators is added by more than three for the examined system. The number of faults in the line decreased by 82% in the first twelve months following the addition of the glass insulator to the pole side, which shows the benefit of the application. That application is essential in terms of reducing the problems in live lines without changing existing insulators.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Thermal Analysis in Power Transmission · High voltage insulation and dielectric phenomena · Lightning and Electromagnetic Phenomena

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (37)

Show source-provided references
1. Computation of ac wet flashover voltage of ceramic and composite insulators10.1109/TDEI.2008.4656243 ↗
2. C. Tourreil, E. Brocard, V. Sklenicka, Cigre Brochure 284: Use of Corona Rings to Control the Electrical Field Along Transmission Line Composite Insulators, Tech. rep., 2005, pp. 1–25.
3. Electric fields on AC composite transmission line insulators10.1109/TPWRD.2007.911127 ↗
4. Comparison of pollution flashover performance of porcelain long rod, disc type, and composite UHVDC insulators at high altitudes10.1109/TDEI.2012.6215112 ↗
5. Comparison of DC pollution flashover performances of various types of porcelain, glass, and composite insulators10.1109/TPWRD.2007.908779 ↗
6. S. Bhutada, J. Shah, G. Dhiman, S. Chetwani, S. Subramanian, P.V. Subba Rao, 3D electric field modelling of UHV class AC composite transmission line insulators, in: 2020 21st National Power Systems Conference, NPSC 2020, Gandhinagar, India, ISBN: 9781728185521, 2020, pp. 1–6, http://dx.doi.org/10.1109/NPSC49263.2020.9331848.10.1109/NPSC49263.2020.9331848 ↗
7. Electric field analysis and experimental evaluation of 400 kV silicone composite insulator
8. 380 kV corona ring optimization for AC voltages10.1109/TDEI.2011.5739444 ↗
9. J. Li, Z. Peng, Y. Feng, X. Fu, T. Xie, Electric field calculation and grading ring optimization of composite insulator for 500kV AC transmission lines, in: Proceedings of the 2010 IEEE International Conference on Solid Dielectrics, ICSD 2010, Potsdam, Germany, ISBN: 9781424479443, 2010, pp. 1–4, http://dx.doi.org/10.1109/ICSD.2010.5567918.10.1109/ICSD.2010.5567918 ↗
10. Influence of volcanic ash contamination on the flashover voltage of HVAC outdoor suspension insulators10.1109/TDEI.2014.6832265 ↗
11. Influence of water and defects on abnormal temperature rise of composite insulator10.1016/j.engfailanal.2022.106134 ↗
12. The need of creating a new nominal creepage distance in accordance with heaviest pollution 500 kV overhead line insulators10.1016/j.engfailanal.2017.12.018 ↗
13. Investigation on the failure analysis of crimped composite insulators used in “V”type string10.1016/j.engfailanal.2018.08.010 ↗
14. Application of grey theory in pollution prediction on insulator surface in power systems10.1016/j.engfailanal.2019.104153 ↗
15. Understanding field failures of composite insulators10.1016/j.engfailanal.2020.104758 ↗
16. Analysis of in-service composite insulators used in overhead railway traction10.1016/j.engfailanal.2019.104227 ↗
17. Heating phenomenon in unclean composite insulators
18. Effect of acidic-fog on performances of HTV silicone rubber with AC energized10.1016/j.engfailanal.2021.105880 ↗
19. Insulation failure caused by special pollution around industrial environments10.1016/j.engfailanal.2019.04.034 ↗
20. Hydrophobic, dielectric and water immersion performance of 9000 h multi-stresses aged silicone rubber composites for high voltage outdoor insulation10.1016/j.engfailanal.2021.105223 ↗
21. Reliability assessment of aged SiR insulators under humidity and pollution conditions10.1016/j.ijepes.2019.105679 ↗
22. Prediction of flashover voltage using electric field measurement on clean and polluted insulators10.1016/j.ijepes.2019.105574 ↗
23. A novel method for prediction of washing cycles of electrical insulators in high pollution environments10.1016/j.ijepes.2021.107026 ↗
24. AC Flashover characteristics and arc development process of glaze ice-covered insulators in natural environment10.1016/j.ijepes.2021.107559 ↗
25. Effects of shed configuration on AC flashover performance of ice-covered composite long-rod insulators10.1109/TDEI.2012.6148519 ↗
26. Accelerated aging studies of silicon-rubber based polymeric insulators used for HV transmission lines10.1016/j.polymertesting.2017.06.015 ↗
27. Influence of sheds damage on the AC pollution flashover performance of different voltage class composite insulators10.1109/ACCESS.2020.2991117 ↗
28. I. Gutman, J. Lungquist, V. Dubickas, L. Carlshem, R. Kleveborn, Design of corona/arcing rings when replacing cap-and-pin insulators by composite insulators, in: XVII International Symposium on High Voltage Engineering, Honnover, Germany, 2011, pp. 1–6.
29. Voltage and E-field distribution of UHV composite insulator with connection of porcelain insulators
30. AC And DC field distributions in glass, RTV-coated glass and composite insulators
31. Improvement of electric field distribution by integrating composite insulators in a 400 kV AC double circuit line in Algeria10.1109/TDEI.2017.006011 ↗
32. Installing insulation jacket to improve outdoor insulation performance of composite insulator10.1109/TDEI.2011.6118638 ↗
33. Optimal design of corona ring on HV composite insulator using PSO approach with dynamic population size10.1109/TDEI.2015.005383 ↗
34. The climatic characteristics of erzindan and the trend analysis of long-term (1930–2020) temperature and precipitation data recorded in Erzincan
35. Turkish Electricity Transmission Corporation, Tech. rep.
36. 2018
37. 2019