journal article·2020-01Open access

Ant-nest corrosion failure of heat exchangers copper pipes

Luca Cozzarini, Lucia Marsich, Chiara Schmid

Abstract

This paper reports on the failure analysis carried out on leaking copper pipes from three different air conditioning systems. Pinhole leaks originating from localized corrosion morphology were reported. Microscopic interconnecting tunnels inside the pipe section were observed; these tunnels were filled with corrosion products. Experimental findings and similarity to previously reported cases pointed out a corrosion mechanism known as “ant-nest corrosion” as failure cause. This type of corrosion could develop in heat exchanger components stored after assembly, during leakage tests or in the initial operational stages. It was shown that an ant-nest corrosion attack could start due to different reasons and propagate in different ways (from the inside or from the outside of the tube). In the first examined case, it was supposed that the hydrolysis of a halocarbon gas circulating in the pipe was the triggering cause of the corrosion event; in the other cases, we ascribed the starting corrosion event to the presence of residual organic contaminants on the external pipe surface.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Corrosion Behavior and Inhibition · Hydrogen embrittlement and corrosion behaviors in metals · Concrete Corrosion and Durability

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (16)

Show source-provided references
1. Copper corrosion in air conditioning systems
2. Copper tubing failure due to ant-nest corrosion
3. Early, corrosion failure of copper tubing used in air-conditioning units10.1002/(SICI)1521-4176(199902)50:2<103::AID-MACO103>3.0.CO;2-B ↗
4. Ant nest corrosion in copper tubes10.3323/jcorr1974.39.6_315 ↗
5. Early corrosion failures in copper heat exchanger tubing
6. Failure analysis of a copper tube in a finned heat exchanger10.1016/j.engfailanal.2015.02.016 ↗
7. Ant nest corrosion – exploring the labyrinth
8. Ant nest corrosion – digging the tunnel
9. Investigating the mechanism behind ‘Ant Nest’ corrosion on copper tube10.3390/ma11040533 ↗
10. Localized corrosion in copper tubes and the effect of anti-tarnishing pretreatment10.1007/BF00728041 ↗
11. Ant-nest corrosion of copper tubing in air-conditioning units10.3989/revmetalm.2006.v42.i5.34 ↗
12. Localized corrosion of copper in wet organic acid vapor10.3323/jcorr1991.44.233 ↗
13. Failure analysis of copper tube used in a refrigerating plant10.1016/j.engfailanal.2013.11.014 ↗
14. Kinetic study of formate compounds developed on copper in the presence of formic acid vapor10.1149/1.2988059 ↗
15. The hydrolysis of halocarbon refrigerants in freeze desalination processes. Part I. Solubility and hydrolysis rates of Freon 114 (CClF2CClF2)10.1016/S0011-9164(00)80177-0 ↗
16. Interactive effect of ant nest corrosion and stress corrosion on the failure of copper tubes10.1016/j.engfailanal.2017.09.013 ↗