Failure analysis of copper tube used in a refrigerating plant
Source abstract
Abstract
Abstract This paper reports the failure analysis of a leaked copper tube used in a refrigerating plant for carrying polyol ester oil for lubrication and cooling of compressor bearings. Failure had occurred at the bent region of the tube in the form of a wide diametric crack. The crack was intergranular and filled with corrosion products. The failed region on the inner diameter side of the tube had red–brown and dull-black surface films which were identified as cuprous oxide. No degradation or decomposition of the lubricant oil was detected. The microscopic examination of the cross-section of the tube showed corrosion degradation on both the outer and inner diameter surfaces with similar morphology. The corrosion morphology consisted of pit tunnels with fine longitudinal cracks bridging individual pitted regions typical of ant-nest corrosion. A few cracks, at the bent region of the tube, had originated through the pits and propagated along the wall thickness. The failure was concluded to be due to ant-nest corrosion of copper in the presence of carboxylic acid. Organic compounds used during the fabrication and joining of the copper tubes, if not properly cleaned, may decompose to carboxylic acid in presence of air and moisture.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Corrosion Behavior and Inhibition · Hydrogen embrittlement and corrosion behaviors in metals · Concrete Corrosion and Durability
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (16)
Show source-provided references
1. Copper deterioration: causes, diagnosis and risk minimization10.1179/095066009X12506721665257 ↗
2. Standard test method for acid and base number by color-indicator titration. D 974, annual book of ASTM standards.
3. Standard practice for condition monitoring of in-service lubricants by trend analysis using Fourier transform infrared (FT-IR) spectrometry. E 2412, annual book of ASTM standards.
4. Standard test method for condition monitoring of oxidation in in-service petroleum and hydrocarbon based lubricants by trend analysis using Fourier transform infrared (FT-IR) spectrometry. D 7414, annual book of ASTM standards.
5. Toms Allison M. Fourier-transform infrared (FTIR) spectroscopy – applying the correct method for your application, society of tribologists and Lubrication Engineers (STLE). 62nd annual meeting, May 6–10, 2007, Philadelphia, Pennsylvania, USA.
6. Corbett RA, Elliott P. Ant-nest corrosion – digging the tunnels. Corrosion 2000 Paper No. 00646. p. 1–15.10.5006/C2000-00646 ↗
7. Elliott P, Corbett RA. Ant nest corrosion – exploring the labyrinth. Corrosion 1999 Paper No. 99342. p. 1–12.10.5006/C2000-00646 ↗
8. Localized corrosion in copper tubes and the effect of anti-tarnishing pretreatment10.1007/BF00728041 ↗
9. Localized ‘ant nest’ corrosion of copper tubing and preventive measures
10. Kinetic study of formate compounds developed on copper in the presence of formic acid vapor10.1149/1.2988059 ↗
11. Early corrosion failures in copper heat exchanger tubing
12. Ant-nest corrosion of copper tubing in air-conditioning units10.3989/revmetalm.2006.v42.i5.34 ↗
13. Effect of different types of alkylaldehyde and crystal grain size on the morphology of a localized corrosion in copper tubes10.1023/A:1018561327446 ↗
14. Air conditioner failure investigation – intergranular cracking in a pure copper condenser tube10.1361/15477020522122 ↗
15. Stress-corrosion cracking in copper refrigerant tubing10.1361/15477020522140 ↗
16. A microstructural aspect of intergranular stress corrosion cracking of semi-hard U-bend tubes of commercially pure copper in cooling systems10.1016/j.engfailanal.2012.07.006 ↗