A Study on the Influence of End-Sheath Aging and Moisture Absorption on Abnormal Heating of Composite Insulators
Source abstract
Abstract
Abnormal heating of composite insulators of high-voltage transmission lines concentrate at its end, especially in a high-humidity environment. In order to study the influence of end-sheath aging and moisture absorption on abnormal heating of composite insulators, in this paper, we first discuss the appearance test, temperature rise test, and dielectric characteristic test conducted on 110 kV decommissioned composite insulators. Test results indicated the temperature rise in composite insulators increased with ambient humidity, but temperature rise was not severely affected by surface contamination of its shed and sheath; in dry environments, the dielectric constant and dielectric loss factor of high-voltage end sheaths are higher than of those of medium- and low-voltage end sheaths, and the loss effect becomes more severe after moisture absorption in a high-humidity environment. After the tests, the authors established a COMSOL simulation model of composite insulators, to analyze changes in the electric field and thermal field of the end sheath of composite insulators due to the coupling of electric and thermal fields. It was concluded that the dielectric constant of a high-voltage end sheath of the composite insulator increased after moisture absorption, distorting the partial electric field on the surface; meanwhile, the dielectric loss factor increased significantly after water molecules intruded into the aging layer of the sheath as polar molecules. Therefore, the dielectric loss (leakage conductance loss and lossy polarization loss) caused by aging and moisture absorption of the sheath surface under partially high field strength in the high-humidity environment was the leading cause of abnormal heating at the high-voltage end of composite insulators. The conclusion of this paper serves as an important reference for revealing the causes of abnormal heating of composite insulators in high-humidity environments and the influence mechanism of external factors on abnormal heating.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: High voltage insulation and dielectric phenomena · Thermal Analysis in Power Transmission · Power Transformer Diagnostics and Insulation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Hainan Power Grid Co., Ltd., Electric Power Research Institute, Haikou 570125, China
Hebei Key Laboratory of Power Transmission Equipment Security Defense, North China Electric Power University, Baoding 071003, China
Funding
Science and Technology Project of China Southern Power Grid Co., Ltd. (Canton, China) · China Southern Power Grid Co., Ltd.
References (21)
Show source-provided references
1. The application and its prospect of silicone rubber composite insulators in China
2. Rapid development of silicone rubber composite insulator in China
3. Application and key technical study of composite insulators
4. Outdoor HV composite polymeric insulators10.1109/TDEI.1999.9286745 ↗
5. Present situation and prospects of applying composite insulators to UHF transmission lines in China
6. Abnormal aged characteristics and causes of sheath-core interface in composite insulators
7. Analysis of operating performance for the 500kV composite insulator
8. Sampling inspection experiment on operating state of transmission line composite insulator
9. Research on heating mechanism of composite insulator of high voltage transmission line
10. Analysis on surface abnormal heating and the countermeasure for composite insulators
11. Effect of damp sheath on abnormal temperature rise at end of composite insulator
12. Influence of environmental humidity on infrared measurement temperature of composite insulators
13. On-line inspection of defective composite insulators by infrared temperature measurement
14. Reason analysis of decay-like aging for composite insulator
15. (2016). Application Rules of Infrared Diagnosis for Live Electrical Equipment: DL/T664-2016, Infraspection Institutes.
16. (1996). Environmental Pollution Classification and External Insulation Selection for High Voltage Transmission Line, Power Plant and Substation: GBT16434-1996, State Technical Supervision Bureau.
17. Aging characteristics of shed materials of silicone rubber composite insulators in service
18. Influence of corona discharge on aging characteristics of HTV silicone rubber material
19. Zhikang, Y. (2019). Deterioration Characteristics and Mechanism of Materials in Composite Insulator under High Humidity, North China Electric Power University.
20. Influence of deteriorated insulator on the electric field distribution of overhang string
21. Infrared detection and thermoelectric coupling simulation analysis of 220 kV insulator abnormal heating10.1088/1742-6596/1659/1/012031 ↗